Pfa Teflon Lined Globe Control Valve
- Place of Origin:
- Wenzhou,China
- Packing:
- Suitable Packing for Sea/Air Transport
- Connection:
- Flange
- Pressure:
- PN10,PN16,150LBS
- Temperature:
- -29℃ ~180℃
A lined control valve blocks volatile gas diffusion through an ultra-dense fluoropolymer barrier that minimizes free volume space within the polymer matrix. When gaseous chlorine, anhydrous hydrogen fluoride, or wet bromine vapors traverse aggressive process pipes, microscopic molecular permeation across thin walls frequently attacks outer steel cavities. Combining thick, uniform liner walls with continuous casting containment restricts vapor movement, stopping subsurface acid condensation and preserving structural pressure boundaries during continuous high-concentration chemical processing.
Body Venting Mechanisms And Liner Collapse Avoidance
Constant vapor permeation across polymer linings generates subsurface gas accumulation behind ductile iron shells. When volatile gases remain trapped between metallic surfaces and internal linings during sudden pipeline de-pressurization events, trapped vapors expand outward, causing severe blister formation and internal jacket inward collapse.
Engineering lined control valves with porous micro-venting plugs provides continuous, safe dispersion routes for permeated vapors. Machined body ports relieve trapped pressure differentials, preserving wall adhesion against outer casings without causing liner separation during operational pressure drops.
Volatile Vapor Permeation Rates And Shell Venting Configurations
| Chemical Process Vapor | Test Temperature Gradient | Permeation Flux Rate | Body Shell Venting Specification |
|---|---|---|---|
| Anhydrous Chlorine Gas | 50°C at 10 bar | Under 0.05 mg / cm²·day | Sintered PTFE micro-plug |
| Wet Hydrogen Chloride | 80°C at 6 bar | Under 0.08 mg / cm²·day | Threaded labyrinth vent hole |
| Gaseous Bromine Stream | 120°C at 4 bar | Under 0.12 mg / cm²·day | Multi-port radial vent path |
Resin Density Optimization And Volumetric Swelling Control
High-temperature halogen streams force volatile molecules into amorphous polymer regions, inducing volumetric swelling that alters internal throttling profiles. Selecting a pfa lined control valve suppresses fluid absorption through tightly controlled spherulitic crystallinity, preserving pristine plug geometry across elevated chemical reaction runs.
Zero-void transfer molding eliminates internal micro-porosity along the seat ring periphery. This dense cross-section prevents chemical absorption, stops seat warping, and ensures stable equal percentage delivery across continuous wet chlorine operations.
Stem Containment Integrity And Single-Seat Shutoff Fidelity
Gaseous chemical streams quickly exploit micro-fissures around sliding stem geometries, producing external fugitive losses through loose bonnet connections. Running a teflon lined globe control valve incorporates extended single-seat galleries that direct aggressive vapors smoothly past wetted trim zones.
Calibrated pneumatic diaphragm actuators supply continuous downward thrust directly over the central seating axis. Rigid structural alignment prevents stem wobbling, suppressing micro-clearance opening while securing ANSI Class VI gas shutoff standards across severe chemical plant headers.
Product Parameter
Materials of Main Parts
| No. | Part Name | Material List | ||||
| 1 | Body/Bonnet | WCB | CF8 | CF8M | CF3 | CF3M |
| 2 | Disc/Stem | 1Cr13 | 1Cr18Ni9 | 00Cr17Ni4Mo2 | 1Cr18Ni9 | 00Cr17Ni4Mo2 |
| 3 | Lining/Seat | FEP PTFE PFA PO | ||||
| 4 | Packing | PTFE | ||||
| 5 | Packing Gland | WCB | CF8 | CF8M | CF3 | CF3M |
Technical Specification
| Seat diameter (mm) | 20 | 25 | 25 | 32 | 32 | 40 | 40 | 50 | 50 | 65 | 65 | 80 | 80 | 100 | 100 | 110 | 125 | 150 | 175 |
| Rated Cv | 5 | 10 | 10 | 16 | 16 | 24 | 24 | 44 | 44 | 68 | 68 | 125 | 125 | 165 | 165 | 195 | 330 | 360 | 460 |
| Rated travel | 16mm | 25mm | 38mm | 50mm | 60mm | ||||||||||||||
| Actual pressure | Maxmum 1.0 MPa (1.6 MPa customised) | ||||||||||||||||||
| Nominal pressure | I.0MPa, 1.6MPa | ||||||||||||||||||
| Working temperature | -29°C-180°C | ||||||||||||||||||
| Trim | Single seat plunger valve core | ||||||||||||||||||
| Flow characteristic | Linear, equal percentage | ||||||||||||||||||
| Adjustable range | 50:1 | ||||||||||||||||||
| Equipped with ZJHA/B Multi-springs Diaphragm Pneumatic Actuators | |||||||||||||||||||
| Model | ZJHA/B-22 | ZJHA/B-23 | ZJHA/B-34 | ZJHA/B-45 | |||||||||||||||
| Action mode | ZJHA type actuator refer to "air-to-close" action: ZJHB actuator refer to "air-to-open" action | ||||||||||||||||||
| Pressure supply | According to the scope of spring: 0.02-0.10, 0.04-0.20, 0.08-0.24 Mpa. Respectly are 0.14, 0.25, 0.35 MPa | ||||||||||||||||||
| Air supply connection | Rc1/4 | ||||||||||||||||||
| Basic error | Without positioner:±5%; With posilioner:±1%; | ||||||||||||||||||
| Backlash | Without positioner: 3%; With positioner: 1%; | ||||||||||||||||||
| Dead zone | Without positioner: 3%; With positioner: 0.4%; | ||||||||||||||||||
| End point deviation | Without positioner: opening point±2.5%, terminal point±5%;closing point±5%, terminal point±2.5%. With positioner error from beginning to end is ±1%; | ||||||||||||||||||
| Travel deviation | ±2.5% | ||||||||||||||||||
| Leakage rate | No more than 10 of rated CV | ||||||||||||||||||
| Optional accessories | positioner, air set, solenoid valve, limit switch etc. (according to the order) | ||||||||||||||||||
Get A Quote
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.